Single-stage Power Line Filter GPF271A-16
Product Description
This single stage EMI filter is designed for various anechoic chambers.It applies to both civil and military EMC test laboratory and can meet the test requirements of CE102,RE102 in US military standard MIL-STD-461E/F and national military standard GJB151B.The series of filter includes three-phase four wires power line filter,400Hz/800Hz power line filter,DC power line filter and so on.
1.Technical Data
Rated Voltage | 250V@50/60Hz (3 phase:250/440V@50/60Hz) | Line/Line Line/Ground |
500V@DC | Line/Line Line/Ground | |
Rated Frequency | DC/50/60Hz | |
Rated Current | Refer to product range table | Ambient temperature of +40℃ |
Number of lines | 2 or 4 | |
Insertion Loss, Per MIL-STD-220C | >100dB | Single-stage filter: 150kHz – 40GHz |
DC Resistance | Refer to product range table | Each Line |
Power Dissipation | Refer to product range table | At Rated Current |
Test Voltage | 1200Vdc,2s | Line/Line |
1200Vdc,2s | Line/Ground | |
Voltage Drop/line | <1% | 250/440V@50/60Hz |
I Leakage | Refer to product range table | |
Discharge Time to Below 34V | 30s | |
Climatic Category(EN 60068-1) | 25/085/21 | -25℃~+85℃ 21 days damp heat test |
Discharging Resistance Integrated
The discharge resistance is integrated into the filter in order to discharge the capacitance after turning off the power.
2. Product Range
Type | Rated Current (A) | Rated Voltage (VAC) | Number of lines | I Leakage (A) | DC resistance of each line (mΩ) | Power Dissipation (W) | Terminal | |
Input | Output | |||||||
GPF271A-16 | 16 | 250 | 2 | 0.7 | <25 | <15 | M6 | M6 |
GPF271A-32 | 32 | 250 | 2 | 1 | <20 | <40 | M6 | M6 |
GPF271A-63 | 63 | 250 | 2 | 1 | <3.0 | <25 | M6 | M6 |
GPF271A-100 | 100 | 250 | 2 | 1 | <1.5 | <30 | M12 | M12 |
GPF271A-150 | 150 | 250 | 2 | 1 | <1.5 | <35 | M12 | M12 |
GPF471A-16 | 16 | 440 | 4 | 0.7 | <50 | <30 | M6 | M6 |
GPF471A-32 | 32 | 440 | 4 | 1 | <20 | <40 | M6 | M6 |
GPF471A-63 | 63 | 440 | 4 | 1 | <3.0 | <35 | M6 | M6 |
GPF471A-100 | 100 | 440 | 4 | 1 | <1.5 | <45 | M12 | M12 |
GPF471A-150 | 150 | 440 | 4 | 1 | <1.5 | <55 | M12 | M12 |
3.Dimensions(mm)
Type | A | B | C | D | E | F | G | H | Dim. |
GPF271A-16 | 600 | 200 | 125 | 184 | 150 | 150 | 60 | M33 | Fig1 |
GPF271A-32 | 600 | 200 | 125 | 184 | 150 | 150 | 60 | M33 | |
GPF271A-63 | 600 | 200 | 125 | 184 | 150 | 150 | 60 | M33 | |
GPF271A-100 | 700 | 240 | 155 | 224 | 180 | 170 | 80 | M45 | |
GPF271A-150 | 700 | 240 | 155 | 224 | 180 | 170 | 80 | M45 | |
GPF471A-16 | 600 | 300 | 125 | 284 | 150 | 150 | 60 | M33 | Fig2 |
GPF471A-32 | 600 | 300 | 125 | 284 | 150 | 150 | 60 | M33 | |
GPF471A-63 | 600 | 300 | 125 | 284 | 150 | 150 | 60 | M33 | |
GPF471A-100 | 700 | 320 | 155 | 304 | 180 | 170 | 80 | M60 | |
GPF471A-150 | 700 | 320 | 155 | 304 | 180 | 170 | 80 | M60 |
4. Circuit Diagrams
Single-stage power line filter |
5. Insertion Loss:
Frequency of 150kHz-40GHz, Insertion loss over 100dB | |
Single-stage filter |
6. Outline Drawing:
Fig1 | Fig2 |